Application and installation method of high-voltage bus duct

02 Apr.,2024

In our daily life, there are always cases where the wires are exposed. In this case, if the wires are crushed or exposed to the sun, it is easy to damage the wires, causing leakage and other dangers. At this time, we need to have equipment to protect the wires. Bus duct is such a device. What are the specific uses of high-voltage bus duct? How does it work? How to maintain the high-voltage bus duc

 

are exported all over the world and different industries with quality first. Our belief is to provide our customers with more and better high value-added products. Let's create a better future together.

Application and installation method of high-voltage bus duct

In our daily life, there are always cases where the wires are exposed. In this case, if the wires are crushed or exposed to the sun, it is easy to damage the wires, causing leakage and other dangers. At this time, we need to have equipment to protect the wires. Bus duct is such a device. What are the specific uses of high-voltage bus duct? How does it work? How to maintain the high-voltage bus duct? Now I will give you one by one answers.

Installation method of high voltage bus duct

1. For horizontal installation of bus channel, the spacing between two supports is ≯ 2500 ㎜, and the vertical installation spacing is ≯ 3600 ㎜;

2. During vertical installation, the mounting bracket shall be drilled with the channel side plate and fastened with M6-M8 bolts.

3. For the installation construction process, the construction scheme from the power feed system to the branch trunk line shall be preferred;

4. Basic installation sequence of enclosed bus duct:

Select the wiring direction → fix the support → fasten the slots with four bolts → add the bus connector plate and insulating pad between the phases → insert the single head bolt into the insulating sleeve → insert the bolt into the bus pre positioning hole → fasten both ends → add half of the upper and lower cover plates → fix the channel on the support.

5. The installation of channel bus, the beginning, middle, terminal and channel shell shall be reliably connected with the grounding grid of electrical equipment. The enclosure of the channel coated with insulating materials shall be connected with flat copper tape or yellow green cables on the grounding bolts between the two channels to ensure that the entire channel is connected as a grounding system.

6. After installation, megger shall be used to test the interphase insulation and grounding insulation resistance of channel bus bar before power transmission: ① LV bus channel shall not be less than 20M Ω; ② The insulation resistance of 6~10KV high-voltage bus channel shall not be less than 1200M Ω. 35KV insulation resistance is not less than 3000M Ω.

7. Before power transmission, the 6~35KV bus channel shall undergo 50HZ power frequency withstand voltage test and DC leakage test, and can be put into operation only after passing the test;

8. For the bus channel put into operation, the bus joint bolts shall be fastened annually within three months, and the bus joint contact condition shall be checked;

Application and installation method of high-voltage bus duct

9. The following items shall be inspected at least once a year for the bus channel in operation:

(1) Fasten each fixing bolt, especially the bus connector, observe whether there is any burning phenomenon caused by poor contact or overcurrent at the connector, and handle it;

(2) The megger shall be used to test the insulation degree and check whether the insulation material is aged;

(3) Connection between bus channel and grounding grid;

(4) Clean the dust and condensate absorbed inside and outside;

10. Precautions:

(1) Before the maintenance of the bus passage, the power distribution cabinet must be cut off first, and hung with the sign of "Someone Operates, Close Strictly" Peugeot, and there should be a special person in front of the cabinet for supervision;

(2) Before the maintenance work starts, the electricity shall be checked and discharged, and the operation can only be carried out after the interphase short circuit and reliable grounding are made with the grounding rod;

Application and installation method of high-voltage bus duct

11. Storage of bus duct:

It should be placed indoors in a dry and ventilated place to prevent moisture, rain and snow, and to prevent dust or foreign matter from entering the passage

High voltage bus duct application

High voltage bus duct is used for electrical connection between transformer and high voltage switchboard, power supply system of large factories and mines, large substations, self owned power plants of large enterprises, and electrical connection between generator and step-up transformer. It can be widely used in power transmission systems below 10KV and below 2000A.

Above, we have introduced the use of high-voltage bus duct and the working principle of high-voltage bus duct in detail. I believe you have a more in-depth understanding of high-voltage bus duct. The subsequent maintenance is also an important factor to determine the service time of the high-voltage bus duct. Therefore, we also need to do a good job in the subsequent maintenance of the high-voltage bus duct.

Click here to get more.

Contact us to discuss your requirements of HOWO Tipping Trailer. Our experienced sales team can help you identify the options that best suit your needs.